Fixed temperature rate-of-rase heat detector

TUP-40



Type:
Conventional, fixed temperature rate-of-rase heat detector

Principle of operation:
The TUP-40 fixed temperature/rate-of-rise heat detector reacts to a rise in temperature occurring during a fire. The detector works as a fixed temperature detector when temperature excesses the threshold pursuant to a given class, and as a rate-of-rise detector during a sudden rise in temperature. In the moment of fire hazard the detector transmits an alarm signal to the fire alarm control panel.

Cooperation:

The TUP-40 detectors can operate in  lines/loops of the IGNIS 1000/2000 or on the side line of ADC-4001M adapter in POLON 4000 fire alarm control panels.

Type

conventional, onesensor, point

Category

to work in normal conditions

Type

temperature

Operational voltage

12 VDC- 28 VDC

Quiescent current consumption

≤ 40 µA

Current consumption in alarm mode

20 mA

Detector class

A1R acc. to PN-EN 54-5

Addressing

conventional detector without addresses

Operating temperature range

from -25°C to 50°C

Relative humidity

to 95% at 40°C

Dimensions of detector with base

Ф115 x 54mm

Weight

0.2 kg

Enclosure colour

white