Fire alarm control panel

IGNIS 2040



The IGNIS 2040 microprocessor based fire detection and alarm control panel is designed for fire detection and fire danger signalling after receipt of a fire signal from interoperating fire detectors and manual call points.
It enables actuation of additional signalling devices and signal transmission to a fire monitoring system. Executed in the Surface Mount Technology, the panel is equipped with expanded diagnostics and self-monitoring circuits that guarantee long-term and unfailing early fire warning system operation.
The control panel is dedicated for fire protection of small premises: warehouses, stores, small offices, remote telecommunication objects (containers), etc.


The following elements can be installed in the control panel detection lines:


a/ 40 and 30 model range fire detectors:

  • • DUR type opti cal smoke detectors,
  • DOR type opti cal smoke detectors,
  • TUP type fi xed temperature/rate-of-rise detectors,
  • DOT type opti cal and temperature detectors,
  • TOP type temperature and fl ame detectors,
  • PUO type fl ame (ultraviolet) detectors,
  • intrinsically safe detectors (pursuant to manufacturer manual),
  • DOP beam smoke detectors


b/ manual fire call points (push buttons):

  • ROP-63 - for indoor use,
  • ROP-63H - for outdoor use.


Main features

  • 4 or 6 detection lines/zones (it is possible to use 2 alarm lines as detection lines) with a possibility to install in each line up to 32 fire detectors or one beam smoke detector, or up to 10 manual fire call points;
  • 2 lines to external signalling devices (that can be used as 2 detection lines);
  • relay outputs from each detection line for external devices control (up to 6 pcs);
  • 1 general alarm relay output;
  • 1 general fault relay output;
  • 1 USB port for a PC connection;
  • 1 output for external devices 24 V power supply;
  •  mains power supply unit with automatic reserve batteries charging circuit;
  •  internal battery panel for reserve power supply for 72 h (from 3,2 Ah to 7 Ah);
  •  permanent battery monitoring with automatic switch off and signalling in the case of discharging;
  •  real time clock;
  •  events memory (up to 999 events);
  •  possibility to program each line alarming as:
  • one-stage or two stage alarm;
  •  one-stage alarm with preliminary reset;
  •  one-stage alarm with zone-ti me coincidence;
  •  monitoring outputs delay time programming;
  •  programming of the control panel operation mode: delays active/disabled;
  •  permanent monitoring of proper functioning of detection lines and signalling line as to break, short circuit and earth fault;
  •  possibility to disable outputs to monitoring and acoustic signalling devices;
  •  detection line disconnection possibility;
  •  possibility to test signalling elements and detectors installed in detection lines;
  •  four levels of access to the control panel handling elements using access codes being typed on the control panel keypad;
  •  comprehensible descriptions and functional servicing elements;
  •  FIRE general signalling with indication of the zone (line) where a fire has occurred;
  •  FAULT general signalling with detailed readout on the LCD panel;
  •  small dimensions (with an internal reserve power supply battery).
  •  esthetic cabinet, in the pastel colour.
Supply voltage: main

50Hz, 230V +10% - 15%

Supply voltage: standby

2pcs. 12V 3.2Ah to 7Ah

Alarm transmission delay time

0 to 10min

Auxiliary devices output current carrying capacity

400mA/24V

Max. signalling line current

180mA/24V

Detection line isolation resistance

or more

Detection line resistance

max 2 x 100Ω

Relay outputs

general damage 1A/30V NC/NO 1pcs.

fire alarm 1A/30V NC/NO 1pcs.

programmable relays 1A/30V NC/NO 6pcs.

Number of detection lines

4 to 6

Compatible manual call points

ROP-63, ROP-63H

Max. number of point detectors in line

32

Max. number of beam detectors in line

1

Max. quiescent current in detection line

max 2mA

Number of signalling lines

to 2

Ingress protection

IP 30

Operating temperature range

from -5°C to 40°C

Dimensions (mm)

311x337x81

Weight

without battery < 4kg

File name Description  
ignis2040da.pdfUser manual

1.3 MB
ignis2040ca.pdfCertificate

981.16 KB
ignis2040k.pdfOthers

165.51 KB

 

Copyrights 2020 POLON-ALFA S.A.  Terms of use