Autonomous ASG-2002 gas detectors range ASG-2000 are designed to detect flammable and toxic gases in hazardous areas such as garage, car parking and boiler room etc. When the particular threshold is exceeded, the detector’s optical indicator is activated and appropriate outputs for controlling the external sounder beacon are activated. It is also possible to start ventilation to vent and remove harmful gases from the room.
Microprocessor detector measurement systems continuously analyze the gas concentration in the room and compare it with the values of the relevant alarm thresholds. Each detector has got three alarm thresholds, strictly related to a defined gas concentration in the air. When the particular threshold is exceeded, the detector’s optical indicator is activated and appropriate outputs for controlling the external sounder beacon are activated. A failure states (detector's failure, sensore's failure, power failure, no sensor module) are signaled by a separate LED and a programmable relay output.
Selection of ASG-2000 detectors:
Model | ASG-2001 | ASG-2001HV | ASG-2002 | ASG-2002HV | ASG-2003 | ASG-2003HV |
Detected gas | CNG (natural gas) (selective methane) | LPG (propane butane) | CO (carbon monoxide) | |||
Sensor module | MSG-6001 | MSG-6002 | MSG-6003 | |||
Type of sensor | semiconductor | semiconductor | electrochemical | |||
Power supply | 9÷30 V DC | 230 V AC | 9÷30 V DC | 230V AC | 9÷30 V DC | 230V AC |
| | |
| | |
| max 60 mA / 24 V | |
| ASG-2002: A1 = 10 % A2 = 20 % A3 = 30 % LEL propane-butane (50 / 50) ASG-2003: A1 = 30 ppm CO (TWA 15 min.) A2 = 60 ppm CO (TWA 15 min.) A3 = 150 ppm (exceeded for at least 60 s) according to PN-EN 50545-1 | |
| | |
Storage conditions | | |
Protection level | | |
| Limitation of common terminal 3A (due to internal connections). |