IGNIS 2500 fire extinguishing control panel is available in single-zone and two-zone versions can operate independently, where each zone has its own extinguishing agent resource or in multi-zone systems with a common extinguishing agent resource. There is also a possibility to combine up to 4 one-zone or two-zone control panels into a multi-zone set.
TECHNICAL DATA | |
---|---|
Number of potential-free relay outputs | 6 |
Number of monitoring inputs | 16 |
Supply voltage: main | 50Hz, 230V +10% - 15% |
Supply voltage: standby | 2pcs. 12V 7Ah to 18Ah |
Programmable inputs | 16 monitoring inputs |
Detection line resistance | max 2 x 120Ω |
Detection line end of line resistor | 1kOhm |
Relay outputs | potential free in control panle 6 load 1A 30V |
Alphanumeric display | LCD 4 x 40 |
Number of detection lines | 2 to 6 |
Number of extinguishing zones | 2 |
Compatible detectors | series |
Max. number of point detectors in line | 32 |
Max. number of beam detectors in line | 1 |
Max. quiescent current in detection line | max 2mA |
Number of supervised potential outputs | 10 |
Number of monitoring lines | 1 or 16 |
Monitoring line termination resistor | 6kOhm +/- 5% |
Max. reserve batteries capacity (2x12V) | 18Ah |
Number of detection zones | 3 |
Ingress protection | IP 30 |
Operating temperature range | from 0°C to 40°C |
Dimensions (mm) | 400x403x183 |
Weight | without battery < 8kg |