Addressable acoustic-optical signaling devices SAB-6006 are designed for acoustic and optical fire signaling by voice. They can work only in addressable detection lines / loops of the POLON 6000 and POLON 4000 fire alarm control panels. For correct operation, the element requires the presence of two supply voltages:
- from the detection line
- from an external power supply.
Electronic circuits of the signaling device with a piezoelectric transducer are placed in a housing made of a red flame retardant material. The housing has a place to put and connect the battery. The signaling device works with the G-40S socket, also made of flame-retardant plastic. The socket is delivered complete with the siren. There is a terminal block in the socket with screwless terminals for connecting installation wires. The terminal block has six terminals, two pairs marked "+" and "-" as the detector line input and output, and two terminals for connecting an external power supply.
Type | optical, voice, acustic, low current |
Installation | internal |
Version | addressable |
Supply voltage | (non-addressable) 9.6VDC - 30VDC |
Supply voltage from detection line | 16.5VDC - 24.6VDC |
Supply voltage of external power supply unit | 9.6VDC - 30VDC |
Current consumption from external power supply | ≤ 170µA with 24 VDC supply with 24 VDC supply |
Power consumption in alarm mode | < |
Sound level | to 103dB |
Operating temperature range | from -25°C to 55°C |
Housing ingress protection | IP 21C |
Dimensions | Ф 115x94 mm |
Weight | 260g |
Other parameters | acc. to PN-EN 54-3 |
File name | Description |
---|