Beam smoke detector

DOP-6001R



Purpose

The DOP-6001 beam smoke detector is designed for smoke detection at the start of a fire. It is especially suitable for protection of indoor spaces, in which the appearance of smoke is likely during ignition of a fire, and where, due to a large space area, installation of a greater number of point smoke detectors would be necessary.

The DOP-6001R beam smoke detectors are equipped with fire alarm and fault relay outputs, which enable them to operate in detection lines of any fire alarm system control panels as well as in burglar alarm systems.

Principles of operation

The DOP-6001 detector consists of an infrared (IR) light transmitter and a receiver located in a single housing and an interoperating E39-R8 prism reflector or 4xE39-R8 reflector panel.

Operation of the beam smoke detector is based on an analysis of air optical transparency in the space between the detector and the prism reflector or the prism reflector panel. If certain defined content of aerosol (smoke) is found in the air reducing optical transparency, then the detector, according to a pre-set sensitivity threshold will evoke an alarm mode. Complete interruption of the radiation beam is signalised as a fault mode because even the largest smoke concentration in the air does not cause complete interruption of the detector optical beam path. If the air is clear, the detector is in a quiescent mode. The DOP-6001 beam smoke detector is equipped with a built-in automatic compensation systems for monitoring of dirt build-up on its optical system and compensation for environ impact conditions ensuring that the detector maintains constant sensitivity and fire detection ability for a long time. At a certain level of dirt build-up, the detector signals a fault mode denoting the necessity to undertake servicing and cleaning works.

During a fire alarm, the detector turns on (usually opened) the breaking circuit of the alarm relay output. In a fault (full break of the radiation beam) and servicing mode (dirt contamination on optical devices), the DOP-6001R detector opens (usually closed) the breaking circuit of the fault relay output. The detector can operate in a support mode or without it.

Installation

The DOP-6001R beam smoke detector and the prism reflector or prism reflector panel are installed on opposite walls of a room. The walls must be stable and vibration-free. Special adjusting screws of the detector unit and the reflector panel are used for precise alignment of the detector and the reflector/s on the optical path. A special laser target viewfinder is activated at the moment when the optical beam path is aligned.

The prism reflector and the panel of prism reflectors are not included in the detector order package and should be ordered separately.

Note

1. For detector testing, the FT-40 test foil should be used; for aligning the detector optical beam path with the reflector panel – the LS-40 service mirror is used.
2. The highest detector sensitivity can be obtained by setting its threshold at 18%.

 

Type

conventional, line

Category

to work in normal conditions

Type

smoke

Operational voltage

9 VDC - 28 VDC

Quiescent current consumption

(9,6 VDC - 28 VDC) 8 - 30 mA

Current consumption in alarm mode

(9,6 VDC - 28 VDC) 20 - 100 mA

Detected test fires

TF1 to TF5 and TF8

Operating temperature range

from -25°C to 55°C

Relative humidity

to 95% at 40°C

Dimensions of detector with base

84 x 128x 79mm

Weight

0.35 kg

Enclosure colour

white

Other parameters

Working range with reflectors unit 4xE39-R8 - 50 to 100m, Working range with reflector E39-R8 - 5 to 50m, Sensitivity thresholds - 18%, 30%, 54%, Laser pointer supply - 6F22 9V battery

File name Description  
DOP-6001R IMM.pdfInstallation and Maintenance Manual

1.04 MB

 

Copyrights 2020 POLON-ALFA S.A.  Terms of use